Unusual PSV Installation
Posted by Piper on Friday June 27, 2008 @ 20:39
Story submitted by Piper
 

Something looks wrong in this photo of a PSV installation:


 

www.pipingdesign.com/imag  es/psv.jpg


 


 

Any comments?

 
Unusual PSV Installation | Plant/Piping Layout | 12 comments

Unusual PSV Installation ( Score: 0, / )
by J Luf on Mon, 30 Jun 2008 08:09:32 -0400

The block Valve on the outlet of the PSV is unusual because you ordinariy want no shutoffs in the outlet piping unless there is some other way of preventing overpressure....  see B3.31.3 and Section VIII Div 1 UG-124=5 (c), UG-126-128 etc etc.